IEC60092 Offshore & Marine Cables | |||
MariTox Marine Flame Retardant Medium Voltage Cables | MariTox Marine Flame Retardant Power & Control Cables | MariFlex Marine Fire Resistant Power & Control Cables | other |
Power Distribution Cables
300V Twisted pairs unshielded Type T signal cables
Construction
Conductor:
Stranded copper conductor tin or alloy coated where necessary for the application , conductor per ASTM or IEC
60228.
Separator tape: optional
Insulation:
Polyvinylchloride(PVC) according to IEEE 1580 2010 Type T,Type X, E, T/N, S, P, LSX and LSE as option.
Pairs:
Jacket:
Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N,
Type T, CP, CPE, L, P or TPO jacket as option (optional for Type P with HD thicknesses).
Armor: optional and shall be nonmagnetic
Sheath:
Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N,
Type T, CP, CPE, L, P or TPO sheath as option (optional except for tinned copper braid armoured cables).
Optional:
For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO
jacket/sheath.
Table B.11—Typical dimensions and weights; twisted-pair signal cable 300 V; Type T unshielded pairs
Number of conductors |
Conductor |
Unarmored | Armored | Armored and sheathed | |||
Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | ||
1 | 20 | 0.28 | 35 | 0.34 | 51 | 0.44 | 88 |
2 | 20 | 0.39 | 58 | 0.45 | 79 | 0.57 | 139 |
3 | 20 | 0.44 | 76 | 0.5 | 100 | 0.62 | 165 |
4 | 20 | 0.48 | 92 | 0.54 | 119 | 0.66 | 189 |
5 | 20 | 0.56 | 127 | 0.62 | 158 | 0.75 | 241 |
6 | 20 | 0.58 | 142 | 0.64 | 173 | 0.77 | 260 |
8 | 20 | 0.64 | 174 | 0.7 | 207 | 0.82 | 298 |
10 | 20 | 0.72 | 210 | 0.78 | 247 | 0.95 | 391 |
15 | 20 | 0.8 | 283 | 0.86 | 323 | 1.03 | 480 |
20 | 20 | 0.91 | 392 | 0.97 | 439 | 1.14 | 610 |
25 | 20 | 1.04 | 477 | 1.1 | 530 | 1.27 | 726 |
30 | 20 | 1.09 | 550 | 1.15 | 606 | 1.32 | 806 |
40 | 20 | 1.22 | 698 | 1.28 | 763 | 1.45 | 989 |
50 | 20 | 1.34 | 845 | 1.4 | 916 | 1.56 | 1151 |
60 | 20 | 1.52 | 1002 | 1.58 | 1082 | 1.81 | 1465 |
1 | 18 | 0.3 | 43 | 0.36 | 59 | 0.46 | 98 |
2 | 18 | 0.42 | 74 | 0.48 | 98 | 0.61 | 166 |
3 | 18 | 0.48 | 98 | 0.54 | 125 | 0.66 | 196 |
4 | 18 | 0.55 | 138 | 0.61 | 167 | 0.74 | 250 |
5 | 18 | 0.61 | 165 | 0.67 | 198 | 0.8 | 289 |
6 | 18 | 0.63 | 186 | 0.69 | 219 | 0.82 | 312 |
8 | 18 | 0.69 | 232 | 0.75 | 267 | 0.92 | 402 |
10 | 18 | 0.78 | 281 | 0.84 | 321 | 1.01 | 471 |
15 | 18 | 0.91 | 424 | 0.97 | 471 | 1.14 | 640 |
20 | 18 | 0.99 | 533 | 1.05 | 583 | 1.22 | 765 |
25 | 18 | 1.13 | 652 | 1.19 | 708 | 1.36 | 912 |
30 | 18 | 1.19 | 758 | 1.25 | 820 | 1.42 | 1034 |
40 | 18 | 1.33 | 972 | 1.39 | 1043 | 1.56 | 1279 |
50 | 18 | 1.46 | 1185 | 1.52 | 1263 | 1.76 | 1637 |
60 | 18 | 1.66 | 1409 | 1.72 | 1498 | 1.96 | 1917 |
1 | 16 | 0.32 | 51 | 0.38 | 69 | 0.48 | 110 |
2 | 16 | 0.45 | 90 | 0.51 | 114 | 0.64 | 185 |
3 | 16 | 0.51 | 121 | 0.57 | 150 | 0.7 | 227 |
4 | 16 | 0.59 | 169 | 0.65 | 200 | 0.78 | 287 |
5 | 16 | 0.66 | 202 | 0.72 | 237 | 0.89 | 369 |
6 | 16 | 0.68 | 231 | 0.74 | 266 | 0.91 | 400 |
8 | 16 | 0.75 | 290 | 0.81 | 327 | 0.98 | 475 |
10 | 16 | 0.89 | 388 | 0.95 | 433 | 1.12 | 604 |
15 | 16 | 0.99 | 532 | 1.05 | 582 | 1.22 | 770 |
25 | 16 | 1.23 | 827 | 1.29 | 892 | 1.46 | 1117 |
30 | 16 | 1.3 | 966 | 1.36 | 1034 | 1.52 | 1261 |
40 | 16 | 1.45 | 1246 | 1.51 | 1322 | 1.74 | 1682 |
50 | 16 | 1.59 | 1524 | 1.65 | 1607 | 1.88 | 1994 |
60 | 16 | 1.88 | 1928 | 1.94 | 2028 | 2.17 | 2491 |
NOTE—These values are for reference purposes only and should not be construed as requirements. Dimensions are based on the use of Class B conductors. Weights of armored constructions are based on aluminum braid armor. It is recommended that the user/specifier contact the manuf acturer for manufacturer specific values.